| Display: | 4 0.40 inch displays + 4 0.30 displays |
| Operating temperature: | 1 relays 8A + 1 Ssr + RS485 |
| Sealing: | IP65 front panel (with gasket) IP30 box, IP20 terminals |
| Material: | Polycarbonate UL94V2 self-extinguishing |
| Weight: | 100g |
| Analogue input: | AN1. Configurable via software. Thermocouple type: K, S, R, J. Automatic compensation of cold junction from 0°C to 50°C. Thermoresistance: PT100, PT500, PT1000, Ni100, PTC1K, NTC10K (β 3435K). Linear: 0-10V, 0-20 or 4-20mA, 0-40mV Potentiometers: 6KΩ, 150KΩ, |
Tolerance (25°C) +/-0.2 % ± 1 digit (full scale) for thermocouple input, thermo- resistance and V/mA. Cold junction accuracy 0.1°C/°C Impedance: 0-10V: Ri>110KΩ 0-20mA: Ri<5Ω 4-20mA: Ri<5Ω 0-40mV: Ri>1MΩ |
| Relay output: | 2 relays (ATR142-ABC) 1 relay (ATR142-ABC-T) Configurable as command and/or alarm output |
Contacts: Q1: 8A-250V~ for resistive loads Q2: 5A-250V~ for resistive loads |
| SSR output: | 1 SSR Configurable as command output and/ or alarm output. |
12Vdc/30mA |
| Supply: | Power supply 24..230 Vac/Vdc +/-15% 50/60Hz |
Power consumption 4.6VA |
| Regulation algorithms: | ON-OFF with hysteresis. P, PI, PID, PD with proportional time |
| Proportional band: | 0...9999°C or °F |
| Integral time: | 0,0...999,9 sec (0 excluded) |
| Derivative time: | 0,0...999,9 sec (0 excluded) |
| Controller functions: | Manual or automatic Tuning, configurable alarms, protection of command and alarm setpoints, activation of functions via digital input, preset cycle with Start/Stop. |
{{.}}