Transmitter LKM263
The LKM263 is a digital, programmable measuring transducer for mounting on the standard rail and can be set for various resistance sensors according to DIN EN 60751. It converts the temperature-dependent resistance value of the sensor into a standard signal of 4...20mA or inverse 20...4mA. Lead resistances are compensated by means of a four-wire circuit. A three- or two-wire circuit can also be implemented.
The transmitter is delivered configured according to the customer's requirements. Subsequent changes of the sensor and measuring range can be made with our communication interface "LKM S1" with adapter A1 and a PC. The required program is available free of charge in the tab "Downloads".
With a zero controller a small correction can be done on site. Additionally an offset can be set by software.
The selection menu is available for configuration.
When entering your individual measuring range, please note the measuring range of the selected sensor. This can be found in the technical data. The minimum span is 20°C.
| Input | Measurement range |
|---|---|
| Pt100 | -200 – 850 °C |
| Pt1000 | -200 – 300 °C |
| Ni100 (TK6180, TK5000) | -60 – 250 °C |
| Ni1000 (TK6180, TK5000) | -60 – 200 °C |
| Resistance | 0 – 400 Ω, 0 – 2000 Ω |
| Feature | Value | Remark |
|---|---|---|
| Input | Pt100, Pt1000, Ni100, Ni1000, resistances | configurable |
| Connection type | 2-/3-/4-wire | configurable |
| Measuring current | 0.25 mA | |
| Current consumption | max. 21 mA | |
| Loop supply voltage | 9 – 35 VDC | reverse-polarity protected |
| Zero | programmable | |
| Span | programmable | |
| Resolution | 14 bit | |
| Measurement accuracy | 0.2 % | depends on measurement range |
| Linearization accuracy | 0.1 % | |
| Measurement rate | 2/s | |
| Output | 4 – 20 mA | configurable, 2-wire current loop |
| Sensor break | > 20 mA | |
| Short-circuit | < 4 mA | |
| Terminal type | Screw terminals | 0.2 – 2.5 mm² |
| Temperature coefficient | 0.015 K/°C | configured temperature range 0 – 100 °C |
| Operating temperature | -25 – 70 °C | |
| Dimensions | 75 × 25 × 52 mm | H x W x D |
| Weight | 60 g | |
| EMC | EN 61326-1 EN 61326-2-3 |
Emission and immunity |
| Document | Format | Language(s) |
|---|---|---|
| Datasheet – LKM263 Technical Specification |
||
| Operating Instructions – LKM263 Installation and operating manual |
| Program / Package | Format | Language(s) |
|---|---|---|
| Service Program – LKM263 for Windows-PCs Parameterization Software |
ZIP | |
| Program – AnalogToTemperatur Conversion of analog output values (mA or V) to temperature |
ZIP |
{{.}}