Transmitter LKM200
The LKM200 is designed for temperature measurements in various industrial applications, where the sensor, measurement range, and output signal can all be individually configured. The four-wire connection for resistance thermometers compensates for lead resistance, but three- and two-wire connections are also possible.
Versatile Connectivity: The LKM200 supports resistance thermometers according to DIN EN 60751, thermocouples according to DIN EN 60584 and DIN 43710, as well as resistances up to 6 kΩ, covering a wide range of analog temperature sensors.
Customizable Output Signal: To ensure maximum compatibility with existing components, an output signal of 4...20 mA or 0...10 V can be set. Individual scaling up to 10 V is also possible for the voltage output signal.
Reliable Sensor Connection: The galvanically isolated sensor connection ensures interference-free measurements, particularly for thermocouples.
Easy Configuration: Use the DIP switches for local configuration without additional hardware or software, or adjust the LKM200 precisely to your needs via the USB-C interface.
| Input | Maximum range | Accuracy |
|---|---|---|
| Resistance | 0 – 6000 Ω | ±0.01 Ω |
| Pt100 | -200 – 820 °C | ±0.02 K |
| Pt1000 | -200 – 850 °C | ±0.02 K |
| Ni100 TK6180 | -60 – 250 °C | ±0.1 K |
| Ni1000 TK6180 | -60 – 250 °C | ±0.1 K |
| Thermocouples | ||
| Type B, Pt30Rh–Pt6Rh | 300 – 1820 °C | ±0.5 K |
| Type C, W5Re–W26Re | 0 – 2315 °C | ±0.5 K |
| Type E, NiCr–CuNi | -150 – 950 °C | ±0.5 K |
| Type J, Fe–CuNi | -200 – 1200 °C | ±0.5 K |
| Type K, NiCr–Ni | -200 – 1370 °C | ±0.5 K |
| Type N, NiCrSi–NiSi | -200 – 1300 °C | ±0.5 K |
| Type R, Pt13Rh–Pt | -50 – 1760 °C | ±0.5 K |
| Type S, Pt10Rh–Pt | -50 – 1760 °C | ±0.5 K |
| Type T, Cu–CuNi | -250 – 400 °C | ±0.5 K |
| Type U, NiCr–Ni | -250 – 600 °C | ±0.5 K |
| Resistance sensor | Thermocouple | |
|---|---|---|
| Linearity error | < 0.01 K | < 0.3 K |
| Cold-junction error | - | ±0.5 °C |
| Span | > 20 K | > 200 K |
| Sensor wiring | 2-, 3- or 4-wire | - |
| Sensors via DIP switch | Pt100 4-wire | Types J, K, N, S |
| Ranges via DIP switch | 15 | 4 each |
| Output 4 – 20 mA | Output 0 – 10 V / 0 – 5 V | |
|---|---|---|
| Sensor break | 20.5 mA | 10.5 V / 5.5 V |
| Sensor short (resistance) | < 4 mA | = 0 V |
| Sensor short (thermocouple) | current value for ambient temperature | voltage value for ambient temperature |
| Note: with inverted output the error behaviour is inverted as well. | ||
| Value | Remark | |
|---|---|---|
| Output signal | 4 – 20 mA, 0 – 5 V, 0 – 10 V | or inverted |
| Output via DIP switch | 4 – 20 mA or 0 – 10 V | |
| Galvanic isolation | 1500 VAC | 1 min |
| Measuring current (resistance) | 0.25 mA | |
| Loop supply | 8.5 – 36 V DC | for current output, reverse polarity protected |
| Supply voltage | 15 – 35 V DC | for voltage output, reverse polarity protected |
| Max. current consumption | 23 mA | at 24 V DC |
| Operating temperature | -40 – 85 °C | |
| Max. ambient humidity | 95 % RH | |
| Temperature coefficient | < 10 ppm / K | |
| Output resolution | 14 Bit | |
| Interface | USB-C | |
| Measurement rate | 2 / s | |
| Input terminals | Screw terminals | 0.2 – 1.5 mm² |
| Output terminals | Screw terminals | 0.2 – 2.5 mm² |
| Mounting | 35 mm DIN rail | |
| Dimensions | 89.7 × 17.8 × 60.7 mm | H × W × D |
| Material | Polycarbonate | |
| Weight | 60 g | |
| Protection class | IP20 | |
| Vibration | 5 g / 10 – 200 Hz | |
| EMC | EN 61326-1 EN 61326-2-3 |
Emission and immunity |
| Document | Format | Language(s) |
|---|---|---|
| Datasheet – LKM200 Technical specification |
||
| Operating Instructions – LKM200 Installation and operating manual |
| Program / Package | Format | Language(s) |
|---|---|---|
| Service program for LKM200 (Windows PCs) Parameterization software |
ZIP | |
| Program – AnalogToTemperatur Conversion of analog output values (mA or V) to temperature |
ZIP | |
| Driver (ftdichip.com) USB driver |